CMS460DCH-4 Laststrom-Monitor mit 3 Messkanälen zur Über-
Load current monitoring in grounded and IT networks
Up to 90 analysis devices via BMS bus
Analysis of harmonics and THD
Adjustable frequency response for fire protection
The CMS460 system consists of one or more CMS460-D load current analyzers, which can measure and analyze load currents in grounded and ungrounded power supply systems using the corresponding current transformers. The maximum voltage of the monitored network depends on the rated insulation voltage of the current transformers used in busbar systems or on the cables or wires installed.
For alternating and pulsed currents, current transformers from the W… (closed), WR… (rectangular), WS… (split), and WF… (flexible) series are used. The various current transformers can be connected to the measurement channels of the analyzers in any combination. Each CMS460-D has 12 measurement channels. A total of up to 90 load current analyzers can be connected via the BMS bus (RS-485 interface with BMS protocol), allowing for the monitoring of up to 1,080 measurement channels (outputs).
For applications in fire and equipment protection, the frequency response can be adjusted accordingly. The measured currents can be analyzed for harmonic distortions.
Features and Functions:
· Selectable AC and pulse current-sensitive measurement for each channel
· RMS measurement
· 12 measurement channels per unit for load current
· Up to 90 CMS… evaluation units in the system (1,080 measurement channels)
· Fast parallel polling for all channels
· Response ranges 100 mA…125 A (42…2000 Hz)
· Preset function
· Adjustable time delays
· Adjustable frequency response (e.g., fire and equipment protection)
· History memory for 300 data records per channel
· Data logger for 300 data records per channel
· Analysis of harmonics, THD
· Two alarm relays, each with one changeover contact
· Selectable operating current/quiescent current and fault memory
· Connection for external test and reset button
· Backlit graphic display (7-segment display) and alarm LEDs
· Data exchange via BMS bus
· Password protection for device settings
· RoHS-compliant
Technical Specifications:
· Rated voltage: 250 V AC
· Number of measurement channels: 3
· Special firmware suitable for Swiss applications
· External current transformers: STW2/STW3/STW4
· Measurement range: 1 A...63 A
· LC display: Backlit graphic display
· History memory: 300 data records
· Data logger: 300 data records per measurement channel
· Connection type: Screw terminals
· Dimensions: W 108 x H 90 x D 74 mm