B.98120003

CTBC35 Measuring current transformer 35 mm

All-current sensitive residual current monitoring
Swiss standard version according to NIN chapter 5.3.2.3

Product description

LINETRAXX MRCDB300 series


The all-current sensitive MRCDB300 device series is used as additional protection (protection against indirect contact) in earthed systems (TN and TT systems) in which DC residual currents or AC residual currents can occur. These systems include, in particular, loads with six-pulse bridge rectifiers or half-wave rectification with smoothing, e.g. converters, chargers, construction machinery with frequency-controlled drives. When the response value IΔn2 (alarm) is reached, the output relays K1 and K2 switch.


By using an MRCDB300 module and a switching element with isolating properties, the device combination meets the requirements for an MRCD protective device in accordance with DIN EN 60947-2 Annex M. The application is specifically intended for protection objectives such as personal protection, fire protection and system protection. The switching element must not exceed a maximum switch-off time of 20 ms. The residual current monitoring modules each consist of the MRCDB300 evaluation electronics and a CTBC20(P)...210(P) series measuring current transformer core.


To assemble a fully-fledged module, both the electronics and a measuring current transformer core are therefore required; if ordered separately, these two components must then be plugged together and calibrated during commissioning Plugged together and calibrated during commissioning and calibrated during commissioning. The CTBC20P...210P series measuring current transformers have integrated magnetic shielding and are suitable for applications with high load or inrush currents.


Features:

- Design of a protective device in accordance with DIN EN 60947-2 Annex M in combination with a circuit-breaker with isolating properties

- Monitoring of the connected circuit-breaker by means of contact feedback

- RS-485 interface with Modbus RTU (read out measured values/parameterization)

- Integrated switching outputs with two changeover contacts K1 and K2 (galvanically isolated)

- Fulfills the protection objectives of personal, fire and system protection (depending on variant)

- Frequency range DC...100 kHz

- Combined test and reset button

- Multi-color LED for operation, response value exceeded, fault and status messages

- Type B AC/DC-sensitive measured value detection in accordance with IEC 60755

- Type B+ all-current sensitive measured value detection in accordance with VDE 0664-400

- Replaceable electronics housing without mechanical separation of the primary conductors

- Expansion/retrofitting or modification of functionalities in the event of changed monitoring requirements

- Insensitive to load current due to magnetic full shield (only CTBC20P...210P)

- Connection monitoring of the measuring current transformer with cyclical test current

- Use of all MRCDB300 for all CTBC... measuring current transformer sizes

- Supply voltage DC 24 V


Possible response values (to be set on the evaluation unit):

- CTBC20, CTBC20P 10 mA...500 mA

- CTBC35, CTBC35P, CTUBC60, CTBC60P 30 mA...10 A

- CTBC120P, CTBC210P 100 mA...10 A

- CTBC120, CTBC210 300 mA...10 A


Commissioning:

Carry out the offset adjustment on the de-energized system.


Scope of delivery: Measuring current transformer core

The appropriate modules must be ordered separately